Table of Contents
When a transformer is supplied with a fixed applied voltage at its primary winding, the secondary terminal voltage does not always remain constant. If the magnitude or power factor of the load connected to the secondary side changes, a corresponding change in is observed. This change occurs due to the voltage drops across the winding resistances and leakage reactances, a phenomenon known as voltage regulation
Voltage Regulation in Transformer
Definition of Voltage Regulation
Voltage regulation of a transformer is defined as:
The percentage change in secondary terminal voltage when the load at a given power factor is varied from no-load to full-load, while the applied primary voltage is kept constant.
Mathematically:

Where:
- = Secondary terminal voltage at no-load
- = Secondary terminal voltage at full-load
Ideal and Practical Voltage Regulation
- Ideal Transformer: There should be no change in the secondary terminal voltage irrespective of the load. Hence, the ideal voltage regulation is 0%.
- Practical Transformer: In reality, due to winding resistance and leakage reactance, the secondary terminal voltage changes with load. Therefore, voltage regulation is always present. A good transformer is designed to keep this regulation as small as possible.
Factors Affecting Voltage Regulation
The change in secondary terminal voltage depends mainly on:
- Load Magnitude – Higher load increases current, which increases voltage drop across winding resistance and leakage reactance.
- Load Power Factor:
- Resistive Load: Causes a moderate drop in secondary voltage.
- Inductive Load: Causes a larger drop because current lags voltage.
- Capacitive Load: May cause a rise in secondary voltage, leading to negative regulation.

Important Observations
- With resistive and inductive loads, the secondary voltage decreases as the load increases.
- With capacitive loads, secondary voltage increases with load, resulting in negative regulation.
- The graphical representation shows how the percentage regulation varies with different load power factors.
Factors Influencing Voltage Regulation
Voltage regulation in a transformer does not depend on a single element—it is influenced by several interconnected factors. Understanding these in depth is important for analyzing transformer performance in real-world systems.
1. Load Magnitude
- The magnitude of load current directly impacts the internal voltage drops across winding resistance (R) and leakage reactance (X).
- At light load, the current is small, so voltage drops (I·R and I·X) are minimal, resulting in better regulation.
- At full load or heavy load conditions, the current increases significantly, causing higher voltage drops and larger deviation between no-load and full-load secondary voltages.
- In distribution transformers supplying residential or industrial areas, evening peak loads often cause noticeable voltage drops, leading to dimmed lights or underperforming equipment.
2. Load Power Factor
- The power factor (PF) of the load is a crucial determinant of the direction and amount of voltage regulation.
- Lagging Power Factor (Inductive Load):
- Current lags the voltage, so the reactive drop (I·X) adds to the resistive drop.
- This increases the overall voltage drop → positive regulation.
- Unity Power Factor (Resistive Load):
- Current is in phase with voltage.
- Only the resistive component (I·R) contributes to the voltage drop.
- Regulation is moderate and usually less than that for lagging loads.
- Leading Power Factor (Capacitive Load):
- Current leads the voltage, so the reactive component (I·X) subtracts from the resistive drop.
- This can lead to negative regulation, where full-load voltage is higher than no-load voltage.
- Practical Impact: Motors (inductive loads) worsen regulation, while capacitor banks can improve it and even cause a slight rise in secondary voltage.

3. Type of Load
The nature of the connected load plays a decisive role in voltage regulation.
- Inductive Load (e.g., motors, transformers):
- High magnetizing requirements.
- Draws lagging current, resulting in poor regulation and noticeable voltage drops.
- Capacitive Load (e.g., capacitor banks, synchronous condensers):
- Provides leading reactive power.
- It can compensate for inductive effects and even cause negative regulation.
- Resistive Load (e.g., heaters, lamps):
- Current is in phase with voltage.
- Voltage drop is proportional only to resistance, leading to moderate regulation.
4. Combined Effect
- In actual distribution systems, loads are usually a mixture of inductive, resistive, and capacitive elements.
- For example:
- A residential area with fans (inductive), lights (resistive), and air-conditioners (inductive with capacitor banks) will show varying regulation during different times of the day.
- Industrial plants with large motors often require capacitor banks to offset poor regulation.
Voltage Regulation from Secondary Side
Voltage regulation of a transformer is one of the most important performance indicators. It shows how much the secondary terminal voltage varies when the transformer goes from no-load to full-load conditions at a constant primary voltage. This variation gives us a clear idea of how effectively the transformer can maintain a stable supply under different load conditions.
Understanding the Terms
Before deriving the formula, let us clarify the terms:
- E₂ (No-load Secondary Voltage): This is the secondary induced EMF when no load is connected to the secondary. In practice, it is very close to the rated voltage of the transformer but slightly higher than the full-load terminal voltage due to the absence of voltage drops in winding resistance and reactance.
- V₂ (Full-load Secondary Voltage): This is the actual voltage available at the secondary terminals when the transformer is supplying its rated load. It is generally lower than E₂ because of internal drops in winding resistance and leakage reactance.
Percentage Voltage Regulation
Voltage regulation is the difference between no-load voltage and full-load voltage, expressed as a percentage of the full-load voltage.
1. Upward Regulation
If we compare full-load voltage (V₂) with no-load voltage (E₂), regulation can be expressed as:
Here:
- Numerator shows the actual voltage drop inside the transformer.
- Denominator normalizes the drop concerning the operating (full-load) voltage.
This representation emphasizes how much higher the no-load voltage is compared to the full-load voltage.
2. Downward Regulation
In most practical contexts, voltage regulation is expressed in terms of the voltage drop from no-load to full-load, i.e., “downward” regulation:

Here:
- The numerator again indicates the voltage drop.
- Denominator uses the no-load induced voltage as the reference.
This form is less common in practice but still useful for theoretical clarity.
Standard Convention
- Unless otherwise specified, the term Voltage Regulation always refers to Regulation Down.
- That means, when we say a transformer has 4% or 5% regulation, it implies:
Practical Meaning
- Positive Voltage Regulation: Indicates that the full-load terminal voltage (V₂) is less than the no-load voltage (E₂). This is the usual case for resistive and inductive loads.
- Negative Voltage Regulation: Occurs when the full-load voltage (V₂) is higher than the no-load voltage (E₂). This happens with leading power factor (capacitive loads), where the reactive component of current compensates for voltage drops.
This gives a clear picture of how much the primary input voltage must be adjusted to maintain the rated secondary output under various loading conditions.
Voltage Regulation in Transformer (Primary Side Calculation)
Voltage regulation can also be calculated from the primary side. At no-load condition, the applied primary voltage V₁ is approximately equal to the induced emf in the primary E₁, since the no-load current is very small and the drop I₀Z₁ is negligible. Using the transformation ratio K, the secondary quantities can be referred to the primary side for regulation calculation.
Step 1: Equivalent Voltages Referred to Primary Side
- E₂ = K × E₁
- V₂ = K × V₁ (at full-load, as referred to the primary side)
Since V₁ ≈ E₁ at no-load, we can express the relation as:
E₂ = K × E₁
V₂ = K × V₁
Step 2: Definition of Voltage Regulation (Primary Side)
The percentage voltage regulation can now be expressed as:
%VR = (E₂ – V₂) / V₂ × 100
This formula gives the regulation when quantities are referred to the primary side.
Step 3: Practical Definition of Regulation
In practice, the input voltage across the primary is adjusted so that the rated secondary voltage is maintained even under different loading conditions.
Thus, voltage regulation can also be defined as:
“The percentage change in input voltage required to be applied across the primary winding to maintain the rated secondary voltage when the load at a given power factor is changed from no-load to full-load.”
Step 4: Extended Expression
If the input primary voltage has to be changed from its rated value V1 to a new value V1′ to maintain the rated secondary terminal voltage, then the regulation becomes:
%VR = (V1′ – V1) / V1 × 100
This equation highlights how much the supply voltage needs to be increased (or decreased) to compensate for the internal voltage drops in the transformer.
Step 5: Influence of Load Power Factor
Similar to the secondary-side calculation, the effect of power factor is significant:
- Lagging Power Factor (inductive load): Voltage drop increases due to the additional reactance effect.
- Leading Power Factor (capacitive load): Voltage drop decreases, and in some cases, the regulation can even become negative.
- Unity Power Factor (resistive load): Voltage drop depends only on resistance.
## Final Expressions
- Referred to Secondary Side:
%VR = (E₂ – V₂) / V₂ × 100 - Referred to Primary Side:
%VR = (V₁′ – V₁) / V₁ × 100
These two forms are mathematically consistent, and both are used depending on the method of analysis.
Calculating Approximate Voltage Drop in Transformer
The numerator in equations represents the voltage drop that occurs as a transformer transitions from no-load to full-load conditions. This drop is an essential parameter because it determines how well a transformer can maintain a constant voltage under varying load conditions. The approximate value of this drop can be obtained using the equivalent circuit parameters of the transformer. Understanding and calculating this is crucial for both transformer design and performance evaluation.
Approximate Equivalent Circuit
To simplify the analysis, we consider the approximate equivalent circuit of the transformer referred to the secondary side. In this approximation, the no-load branch (consisting of R0 and X0) is omitted, since it contributes very little to the overall voltage drop and can be neglected without significant loss of accuracy. The simplified circuit is illustrated in.
The voltage equation for this simplified circuit becomes:

E2 = V2 + I2 (R02 + jX02)
Where:
- R02 = R2 + R′1 → Equivalent resistance referred to the secondary side
- X02 = X2 + X′1 → Equivalent leakage reactance referred to the secondary side
This relationship shows that the induced emf E2 is the sum of the secondary terminal voltage V2 and the voltage drop across the equivalent series impedance. Here, I2 is the secondary current, and the terms clearly separate the resistive and reactive drops. By analyzing this simplified form, one can more easily calculate the approximate voltage regulation and predict transformer performance under load conditions.
Phasor Diagram
The phasor diagram gives a clearer picture of the relationship between the voltages and current in the transformer. For a lagging power factor load (inductive load), the phasor diagram is shown in Fig.

Steps to construct the Phasor Diagram:
- Draw an arc with radius OA = |E2|, using O as the center.
- Extend line OB = |V2| to intersect this arc at point C. Since OA = OC, the phasor lengths are equal.
- From point A, draw a perpendicular to line OC, intersecting it at point D.
- The approximate voltage drop is then:
(E2 – V2) ≈ (OD – OB)
From the geometry of constructed triangles, we obtain:
(E2 – V2) = (BF + GH)
Where:
- BF = I2 × R02 × cosφ
- GH = I2 × X02 × sinφ
Thus:
(E2 – V2) = I2 (R02 cosφ + X02 sinφ)
This makes it clear that both resistance and leakage reactance contribute to the voltage drop.
Voltage Drop for Leading Power Factor (Capacitive)
When the load is leading (capacitive), the component due to leakage reactance reduces the overall drop. In this case, the voltage drop is given by:
(E2 – V2) = I2 (R02 cosφ – X02 sinφ)
This indicates that capacitive loads can actually improve regulation and even result in negative regulation.
General Expression for Voltage Drop
Combining both cases, we can write a general expression:
(E2 – V2) = I2(R02 cosφ ± X02 sinφ)
Where:
- + sign → Inductive load (lagging power factor)
- – sign → Capacitive load (leading power factor)
This form makes it convenient to handle any type of load in calculations.
Voltage Regulation Formula
The percentage voltage regulation is defined as:
% Voltage Regulation = ((E2 – V2) / V2) × 100
Or, substituting the equivalent circuit expressions:
% Voltage Regulation = (I2 (R02 cosφ ± X02 sinφ) / V2) × 100
(Equation 3.24 – 3.26)
This expression is widely used in practice because it connects measurable transformer parameters with performance.
Special Cases
- Resistive Load (cosφ = 1, sinφ = 0):
(E2 – V2) = I2 × R02 → Only resistive drop is present. - Inductive Load (lagging):
Causes a larger positive voltage drop. Regulation is positive. - Capacitive Load (leading):
It can cause the secondary voltage to rise, giving negative regulation.
Percentage Resistance and Reactance Drops
It is often useful to express the drops separately in percentage form:
%R = (I2 × R02 / V2) × 100
%X = (I2 × X02 / V2) × 100
Thus, the general voltage regulation formula simplifies to:
% Voltage Regulation = (%R cosφ ± %X sinφ)
(Equation 3.27)
These quantities provide a quick method for estimating regulation once %R and %X are known.
Practical Importance
- In power systems, accurate prediction of voltage regulation is critical for ensuring supply quality.
- High positive regulation can cause voltage drops at consumer ends, affecting sensitive equipment.
- Negative regulation, though sometimes useful, can be problematic if it leads to overvoltage conditions.
- Designers optimize winding resistance and leakage reactance to achieve the desired balance between efficiency and regulation.
Key Takeaways
- The approximate voltage drop is obtained from the equivalent circuit, where the no-load branch is ignored.
- The drop depends on both the magnitude of load current and the load power factor angle.
- Inductive loads increase regulation (positive), while capacitive loads can reduce it (negative).
- Expressing results in terms of %R and %X makes analysis simpler and allows easier comparison between transformers.
- A clear understanding of these drops helps engineers design transformers with better performance and reliability, ensuring consistent voltage delivery under varying load conditions.
Improving Voltage Regulation in Transformers
Voltage regulation is not just a theoretical concept—it has practical importance in ensuring a transformer delivers a stable voltage under varying load conditions. Poor regulation can lead to equipment malfunction, heating, reduced efficiency, or even damage to sensitive devices. Hence, improving voltage regulation is a key design and operational goal.
Methods to Improve Voltage Regulation
1. Tap-Changing Transformers
- On-Load Tap Changer (OLTC): Adjusts the transformer winding ratio automatically while the transformer is in service, maintaining nearly constant output voltage.
- Off-Load Tap Changer: Used when voltage variation is relatively small. The tap position is manually changed when the transformer is de-energized.
These mechanisms allow fine-tuning of secondary voltage according to load and supply conditions.
2. Automatic Voltage Regulators (AVR)
An AVR monitors the output voltage of a transformer and adjusts excitation or switching mechanisms to stabilize the voltage. This ensures that consumers receive a consistent supply, even when the load varies.
3. Capacitor Banks and VAR Compensation
By installing capacitor banks, the reactive power demand is reduced. This minimizes voltage drop across the transformer reactance and leads to better regulation. Capacitor banks are particularly useful in industrial installations where inductive loads dominate.
4. Reactive Power Management
Advanced methods like STATCOMs, SVCs, and other FACTS devices provide dynamic VAR compensation, improving power factor and reducing voltage fluctuations.
5. Proper Transformer Design
- Using low-resistance windings
- Reducing leakage reactance through optimized core and coil design
- Using high-grade core material for minimal losses
These measures improve the inherent voltage regulation of the transformer.
Practical Importance
- Distribution Transformers: Stable supply for households and commercial users.
- Industrial Applications: Sensitive machines require tight voltage control.
- Power Systems: Helps maintain grid stability and reliability.
By applying the above methods, voltage regulation can be significantly improved, resulting in better efficiency, stability, and consumer satisfaction.
Applications & Real-World Importance of Voltage Regulation
Voltage regulation is not just a theoretical parameter—it has immense practical importance in ensuring a stable and efficient power supply. Let us explore some key applications and real-world contexts where voltage regulation plays a critical role:
1. Distribution Transformers (Lighting Loads)
In residential and commercial areas, distribution transformers supply power to lighting systems, appliances, and other sensitive devices. If voltage regulation is poor, consumers may experience dim lights, frequent flickering, or damage to electronic devices. Good regulation ensures steady illumination and a safe operating environment.
- Example: A street lighting system connected through a distribution transformer will operate reliably only if the voltage remains within permissible limits.
2. Industrial Applications (Motors, Welding Transformers)
Industries heavily rely on motors, induction machines, and welding transformers. These devices are highly sensitive to voltage variations. Poor regulation can cause:
- Excessive heating in motors.
- Reduced torque and efficiency.
- Unstable welding arcs leading to poor product quality.
Maintaining proper voltage regulation improves motor life, welding consistency, and overall plant productivity.
3. Power Systems and Grid Stability
In large power systems, voltage regulation is directly linked to grid stability. Any sudden drop in voltage due to load changes can trigger a cascade of issues across the network. Stable regulation ensures:
- Smoother integration of renewable energy sources.
- Balanced supply for urban and rural areas.
- Prevention of blackouts and brownouts.
4. Procurement and Transformer Testing
When utilities or industries purchase a transformer, the voltage regulation specification is a key parameter in tender documents. It indicates how well the transformer will perform under real-world load conditions. During factory testing, manufacturers measure regulation to verify compliance with standards.
- A transformer with better regulation is usually preferred as it delivers more consistent performance.
5. Consumer-End Benefits
Finally, good voltage regulation benefits the end-users directly:
- Fewer fluctuations in household appliances.
- Increased lifespan of sensitive equipment like computers and refrigerators.
- Better quality of power supply, leading to consumer satisfaction.
FAQ
What is an acceptable % voltage regulation for a distribution transformer?
A distribution transformer generally has a regulation between ±3% to ±5%, depending on its size and design. Good regulation ensures stable lighting loads, fewer voltage fluctuations, and better consumer satisfaction.
Why can voltage regulation be negative?
Voltage regulation becomes negative when the secondary voltage at full load (V₂) is higher than the no-load induced EMF (E₂). This usually happens under a leading power factor load (capacitive) where reactive effects cause the voltage to rise.
How does power factor affect transformer regulation?
At lagging power factor (inductive loads): Voltage drop increases, giving positive regulation.
At leading power factor (capacitive loads): Voltage may rise, leading to negative regulation.
At unity power factor (purely resistive): Drop depends only on copper resistance.
This shows that power factor correction is a key strategy for maintaining good regulation.Is lower voltage regulation always better?
Yes, in most cases, lower regulation is preferred as it indicates the transformer maintains nearly constant voltage under load. However, extremely low or negative values are not always desirable, since they may signal overcompensation or instability in certain operating conditions.
Why do engineers test voltage regulation before procurement?
Voltage regulation tests are part of acceptance and performance checks for transformers. They ensure that the unit can deliver stable secondary voltage under varying loads, making it suitable for distribution networks, industrial plants, and grid applications.